30KW Resistive Load Bank For IEC 62040-3 UPS Test
Products Description
30KW Resistive Load Bank for IEC 62040-3 UPS Test
Equipment Overview:
This electric energy load testing device is easy to operate, small in size and convenient to transport. Depending on the load capacity, multiple units can be used in parallel. The control method is divided into manual button control.
Based on the requirements of IEC 62040-3 ED 2.0 2005 Annex C, figure C.1 and C.2, we have designed the load cabinet as following parts:
A set of resistive load, the resistive load is 30KW, the rated voltage is AC220V/60HZ, at the same time meet the single-phase AC127V/60HZ power supply test, the capacity can also reach 30KW.
Technical Parameters:
Power supply from test sample: If the power supply from the test sample is three phases, then all the GA, GB, GC and N terminals should be connected to test sample correspondingly (GA+GB+GC+N); if the power supply from the test sample is single phase, then one of the GA, GB, GC terminals plus N terminal should be connected to test sample correspondingly (such as GA+N terminals).
Power supply from mains: the power supply from mains should be three phases AC220V/60Hz, the power supply is for the control components of this load bank. Operator should remove the lower three wires from the lower three terminals, and wrap up them well. Then operator uses the power supply cord we’ve offered to connect to the mains (L1+L2+L3+PE). The load bank must be grounded reliably before use.
System composition
Load cabinet, resistive load, on-site data acquisition, manual load/unload control, electrical control part, heat sink and auxiliary control, etc.
Total discharge power
Resistive 30KW (designed according to three phase 220V/60HZ); at the same time meets 30KW single-phase 127V/60HZ (the current carrying capacity of the neutral line is the sum of the three-phase carrying capacity)
Resistive load binning
30KW total 6 gearsAny adjustment by combinations within 1KW-30KW power range (minimum step 1KW): 1KW, 2KW, 2KW, 5KW, 10KW, 10KW.
Test voltage
Three-phase AC220V/single-phase AC127V
Remark: Single and three-phase load test cannot be used at the same time
Test frequency
60HZ
Resistance tube
Each resistance element: insulation resistance above 500MΩ, withstand voltage AC2000V for 1-minute, high temperature resistance
Load characteristics
Resistive load
Contactor
China brand contactor
Breaker
China brand breaker
Heater
Wuxi Zhuxing
Power Factor
1.0
Load connection
Y
Loading accuracy
±3%;
Three-phase balance
The unbalance degree is less than or equal to 3%;
Way of working
Continuously working
Power supply
AC220VAC/60HZ/three-phase four-wire system; (reserved wiring terminals)
Cooling method
Forced air cooling
Way to control
Manual button control
Insulation class
F
Detection function
Real-time display of voltage, current, power, frequency, power factor, etc.
Load protection
Short circuit, over current, high temperature, low air volume and fan failure protection
Fault alarm
There is fan failure, load high temperature alarm
Load cabinet dimensions
L700mm×W800mm×H1000mm (L×W×H), with pulley (height 150MM)
Weight
172KG
Installation location
Indoor